AC90 (–40°C) XLPE 600 Volts 90°C Copper

 

 

 

 

Two, three or four copper conductors with low temperature insulation (RW90 XLPE) and bare copper bonding wire. Conductor assembly paper wrapped and covered with bare interlocked aluminum armour. Rated 600 volts. CSA Spec C22.2 No. 51-M89

Applications:

ECS
Catalogue
Number
Conductor Bonding Wire AWG Size Insulation
(inches)

Ampacity

(30°C Ambient)
(amps)

Nominal
O.D.
(inches)
Total
Weight
(lbs/km)
No. AWG
Size
Stranding
AC14-02-99 2 14 Solid 14 .030 15 .47 213
AC14-03-99 3 14 Solid 14 .030 15 .49 377
AC14-04-99 4 14 Solid 14 .030 15 .52 449
AC12-02-99 2 12 Solid 14 .030 20 .51 275
AC12-03-99 3 12 Solid 14 .030 20 .53 475
AC12-04-99 4 12 Solid 14 .030 20 .56 574
AC10-02-99 2 10 Solid 12 .030 30 .55 335
AC10-03-99 3 10 Solid 12 .030 30 .57 640
AC10-04-99 4 10 Solid 12 .030 30 .62 784
AC08-03-99 3 8 7 Strand 10 .045 45 .75 1,115
AC08-04-99 4 8 7 Strand 10 .045 45 .73 1,165
AC06-03-99 3 6 7 Strand 8 .045 65 .84 1,558
AC06-04-99 4 6 7 Strand 8 .045 65 .93 1,919
AC04-03-99 3 4 7 Strand 8 .045 85 .95 2,132
AC04-04-99 4 4 7 Strand 8 .045 85 1.03 2,674
AC03-03-99 3 3 7 Strand 6 .045 105 1.00 2,624
AC03-04-99 4 3 7 Strand 6 .045 105 1.11 3,297
AC02-03-99 3 2 7 Strand 6 .045 120 1.06 3,116
AC02-04-99 4 2 7 Strand 6 .045 120 1.18 3,937
AC01-03-99 3 1 19 Strand 6 .045 140 1.20 3,658
AC01-04-99 4 1 19 Strand 6 .045 145 1.41 4,806
AC001-03-99 3 1/0 19 Strand 6 .055 155 1.28 4,527
AC001-04-99 4 1/0 19 Strand 6 .055 155 1.51 5,807
AC002-03-99 3 2/0 19 Strand 6 .055 185* 1.38 5,479
AC002-04-99 4 2/0 19 Strand 6 .055 185* 1.63 6,939
AC003-03-99 3 3/0 19 Strand 4 .055 210 1.49 6,808
AC003-04-99 4 3/0 19 Strand 4 .055 210 1.92 8,760
AC004-03-99 3 4/0 19 Strand 4 .055 235 1.61 8,268
AC004-04-99 4 4/0 19 Strand 4 .055 235 1.98 11,138

 

**Copper bonding wire supplied with copper conductors. Aluminum bonding wire supplied with aluminum conductors.

*For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity for sizes #6, #2 and #4/0 AWG aluminum shall be 60, 100 and 200 amperes respectively. #2/0 AWG copper shall be 200 amperes. In these cases, the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.

Assuming 4th conductor is the neutral of a balanced 3 phase 4 wire system

 

Application:
For open and concealed wiring in dry locations only. For use in cabletroughs and ventilated flexible cableways in dry locations only. Minimum recommended installation temperature minus 40°C (with suitable handling procedures).
Maximum conductor temperature 90°C. Approved for use with ceiling fixtures.